Reasons and solutions for the abnormal operation of the speed top valve

Source: SUBITOP Intelligent Control System Popularity:802 Publication time:2019/12/30 09:43:16 Small Middle Big
The reason why various fruits and vegetables in air-conditioning equipment can maintain a fresh and nutritious state for a long time is inseparable from the control of temperature, humidity and other factors in the storage environment. As the pneumatic regulating valve plays an important role in regulating the equipment, its working state naturally requires more attention. Let's take a look at the reasons and solutions of the equipment's regulating valve not running normally.
1, stuck




The problem that often occurs in the regulating valve of air-conditioning equipment is jamming, which often occurs in the new commissioning system and in the initial stage of overhaul operation. Due to the blockage of welding slag and rust in the pipeline at the throttle and the guide, the medium cannot flow smoothly, During the maintenance of the regulating valve, the packing is too tight, which causes the friction to increase, which causes the small signal not to act and the large signal to overshoot.




Solution: You can quickly open or close the auxiliary line or regulating valve of the air-conditioning equipment, and let the dirt be washed away by the medium from the auxiliary line or the ball valve. Another method is to use a pipe wrench to clamp the valve stem, and in the case of external signal pressure, turn the valve stem forward and backward to make the valve core flash over the card. If not, increase the pressure of the air source and increase the driving power. Repeatedly moving up and down several times can solve the problem. If it still does not work, it needs to be dismantled.








Pneumatic control valve








2, leak




气动 Pneumatic regulating valve of air-conditioning equipment leaks, and the length of the valve stem is uncomfortable. Air opening valve, the valve stem is too long, and the upward (or downward) distance of the valve stem is insufficient, resulting in a gap between the valve core and the butterfly valve seat, which cannot be fully contacted, resulting in inadequate closing and leakage. Similarly, the valve stem of the gas shut-off valve is too short, resulting in a gap between the valve core and the valve seat, which cannot be fully contacted, resulting in incomplete closing and leakage.




Solution: The valve stem of the regulating valve of the air-conditioning equipment should be shortened (or extended) to make the regulating valve length appropriate so that it will no longer leak.








3, oscillation




The spring stiffness of the regulating valve of the air-conditioning equipment is insufficient, and the output signal of the regulating valve is unstable and the fluctuation of the fluorine-lined rubber-lined valve is easy to cause the regulating valve to oscillate. It is also said that the frequency of the selected valve is the same as the frequency of the system or the pipe and the base are vibrated violently, which will cause the regulating valve to vibrate accordingly. Improper selection, there is a sharp change in flow resistance, flow rate, and pressure when the valve is operated at a small opening. When the valve rigidity is exceeded, the stability becomes poor, and oscillation occurs when it is serious.








Solution: As the causes of air-conditioning equipment oscillations are multi-faceted, specific problems are analyzed in detail. Slight vibrations can be eliminated by increasing stiffness. For the ceramic valve, if a spring with large rigidity is selected, the piston is used to execute the structure. Vibration of pipes and pedestals eliminates vibration interference by increasing support; if the frequency of valve selection is the same as the system frequency, valves of different structures are replaced; oscillations caused by small openings are caused by improper type selection and large C value. To re-select the flow capacity C value is smaller or use split-range control or son-mother valve to overcome the control valve working at a small opening.




Through more than 10 years of valve use experience in the air-conditioning industry, the advantage of the Speed Top butterfly valve is that the use of special rubber is very clever to avoid similar situations, and the air-conditioning butterfly valve has been specially customized in the air-conditioning industry to prevent rubber and butterfly plates. Dry friction between them, and special improvements made on the actuator, effectively avoiding the valve is not tightly closed and stuck, and the material is also energy-saving and environmentally friendly.
The above are the reasons and solutions for the failure of the pneumatic control valve of the Stopol air-conditioning equipment to operate normally. We also hope that we will pay more attention during the normal maintenance of the equipment, and at the same time in the subsequent use, once these problems occur, we must solve them in time to avoid The fresh-keeping effect of stored fruits and vegetables has an impact, causing large economic losses.